通过Modbus RTU与Watlow F4进行Matlab串行通信_Matlab_Controller_Timeout_Serial Communication_Modbus - Fatal编程技术网

通过Modbus RTU与Watlow F4进行Matlab串行通信

通过Modbus RTU与Watlow F4进行Matlab串行通信,matlab,controller,timeout,serial-communication,modbus,Matlab,Controller,Timeout,Serial Communication,Modbus,我试图通过Modbus RTU在Matlab和Watlow F4温度控制器之间建立通信 到目前为止,我的代码如下所示: obj = serial('COM4'); fopen(obj); set(obj, 'BaudRate', 9600); set(obj, 'Terminator', 'CR'); set(obj, 'Timeout', 100); set(obj, 'InputBufferSize', 3000); 现在我正在读寄存器100。控制器的地址为1 fwrite(obj, [1

我试图通过Modbus RTU在Matlab和Watlow F4温度控制器之间建立通信

到目前为止,我的代码如下所示:

obj = serial('COM4');
fopen(obj);
set(obj, 'BaudRate', 9600);
set(obj, 'Terminator', 'CR');
set(obj, 'Timeout', 100);
set(obj, 'InputBufferSize', 3000);
现在我正在读寄存器100。控制器的地址为1

fwrite(obj, [1 3 00 100 0 1 197 213]);
fread(obj, 7);
但随后会出现以下错误:

Warning: Unsuccessful read: The specified amount of 
data was not returned within the Timeout period. 
你们中有人有过这种交流的经验吗?你知道是什么解决了这个问题吗? 不幸的是,Watlow的支持无法帮助我进行沟通


谢谢

更换一个损坏的RS232/USB适配器解决了问题。顺便说一句,如果有人遇到同样的问题,我描述的消息可能是正确的,通信工作如下:)

您的Modbus请求不正确。从属id后的字节应包含请求的寄存器数和CRC。构建您自己的Modbus请求和响应的良好起点如下:。Mathworks文件交换也有几个例子:感谢您的回复!你确定吗?在我的例子中:1-从机地址3-读取00 100=00 64十六进制的功能代码3-寄存器100,第一个寄存器的数据地址0 1-读取197 213=C5 D5十六进制的寄存器数-CRC,因此由于您的第一个链接只是Modbus,这应该是正确的顺序吗?