如何使用OPCAutomation.dll从kepware连接和读取值

如何使用OPCAutomation.dll从kepware连接和读取值,dll,plc,opc,Dll,Plc,Opc,我正在创建一个小型c#程序,使用OPCAutomation.dll从kepware服务器连接和读取值,但无法获取其语法 OPCAutomation.OPCServer _OPCServer = new OPCAutomation.OPCServer(); _OPCServer.connect("", ""......); 这些括号内的值是什么 OPCAutomation.OPCServer _OPCServer = new OPCAutomation.OPCServer(); _OPCServ

我正在创建一个小型c#程序,使用OPCAutomation.dll从kepware服务器连接和读取值,但无法获取其语法

OPCAutomation.OPCServer _OPCServer = new OPCAutomation.OPCServer();
_OPCServer.connect("", ""......);
这些括号内的值是什么

OPCAutomation.OPCServer _OPCServer = new OPCAutomation.OPCServer();
_OPCServer.connect("Kepware.KEPServerEX.V5", "");
第二个参数是OPC服务器节点,可以保留String.Empty

从反射器:

public virtual extern void Connect([In, MarshalAs(UnmanagedType.BStr)] string ProgID, [In, Optional, MarshalAs(UnmanagedType.Struct)] object Node);
我正在添加一个EXPLAME来读取和写入值:

// set up some variables
OPCServer ConnectedOpc = new OPCServer();
Array OPCItemIDs = Array.CreateInstance(typeof(string), 10);
Array ItemServerHandles = Array.CreateInstance(typeof(Int32), 10);
Array ItemServerErrors = Array.CreateInstance(typeof(Int32), 10);
Array ClientHandles = Array.CreateInstance(typeof(Int32), 10);
Array RequestedDataTypes = Array.CreateInstance(typeof(Int16), 10);
Array AccessPaths = Array.CreateInstance(typeof(string), 10);
OPCGroup OpcGroupNames;

// connect to KepServerEX
ConnectedOpc.Connect("Kepware.KEPServerEX.V5", "");

// Add tags and OPC group.
// set up the tags
OPCItemIDs.SetValue("Counting.PLC.Station1.LoggedON", 1);
OPCItemIDs.SetValue("Counting.PLC.Station2.LoggedON", 2);
OPCItemIDs.SetValue("Counting.PLC.Station3.LoggedON", 3);
OPCItemIDs.SetValue("Counting.PLC.Station1.Operator", 4);
OPCItemIDs.SetValue("Counting.PLC.Station2.Operator", 5);
OPCItemIDs.SetValue("Counting.PLC.Station3.Operator", 6);

// set up the opc group
OpcGroupNames = ConnectedOpc.OPCGroups.Add("Group01");
OpcGroupNames.DeadBand = 0;
OpcGroupNames.UpdateRate = 100;
OpcGroupNames.IsSubscribed = true;
OpcGroupNames.IsActive = true;
OpcGroupNames.OPCItems.AddItems(6, ref OPCItemIDs, ref ClientHandles, out ItemServerHandles, out ItemServerErrors, RequestedDataTypes, AccessPaths);

// Read the values from the server for those tags.
// read
Array ItemServerReadValues = Array.CreateInstance(typeof(string), 10);
object a;
object b;
OpcGroupNames.SyncRead((short)OPCAutomation.OPCDataSource.OPCDevice, 6, ref ItemServerHandles, out ItemServerReadValues, out ItemServerErrors, out a, out b);
Console.WriteLine((string)ItemServerReadValues.GetValue(4));
Console.WriteLine((string)ItemServerReadValues.GetValue(5));
Console.WriteLine((string)ItemServerReadValues.GetValue(6));

// Write some values into the server for those tags.
// write
Array ItemServerWriteValues = Array.CreateInstance(typeof(object), 7);
ItemServerWriteValues.SetValue(1, 1);
ItemServerWriteValues.SetValue(1, 2);
ItemServerWriteValues.SetValue(1, 3);
ItemServerWriteValues.SetValue("Test Op 1", 4);
ItemServerWriteValues.SetValue("Test Op 2", 5);
ItemServerWriteValues.SetValue("Test Op 3", 6);
OpcGroupNames.SyncWrite(6, ref ItemServerHandles, ref ItemServerReadValues, out ItemServerErrors);

此示例改编自:,我添加了它以防链接断开。

谢谢@jdecuper,我知道上面的代码是用于连接kepware的,除此之外,我还需要使用语法从Same读取标记值。这是一个很好的入门示例: